TP48200A D12A1(800×700×1200mm) system brochure


Чтобы посмотреть этот PDF файл с форматированием и разметкой, скачайте его и откройте на своем компьютере.
General

Dimensions of cabinet

1200 (H,47.24in.excluding the pedestal)
×
700(W,27.56in.)
×
800
(D,31.49in.) mm

Dimensions of pedestal

100 (H,3.94in.)
×
700(W,27.56in.)
×
800 (D,31.49in.) mm

Weight


100Kg (without rectifier modules)

Rated capacity

200A

Number of rectifier

2~4

Cooling mode/power


Direct ventilation/Rated power1400W,Maximum power1700W


Installation mode

Wall
-
mounted;
ground installation

User space/useful depth

8U/530mm

Protection level

IP45

TP48200A Outdoor

System

Introduction

TP48200A is an AC/DC outdoor power system that configures 48V/50A rectifier modules to
supply rated of 200A output current. The system has excellent performance such as wide
range of AC input voltage, high power efficiency, surge protection, temperature control,
intelligent battery management, and remote monitoring. The TP48200A is used in class B
environment and is optimized for various outdoor scenarios.

Environmental specification

Operating
temperature

-

33 ~ +50


Operating humidity

5% ~ 95% (non
-
condensing)

Altitude

0 ~4000 m (at the altitude from 2000m to 4000m, the temperature
declines by 1


for each increase of 200m in altitude)

www.huawei.com

The system complies with the CE standards,
the power distribution components comply
with the CE and 3C, the PSU complies with
the UL, CE and TUV , the PMU complies
with CE, YD/T 1058
-
2007, and
RoHS

High surge protection Level: Class B

High power efficiency of rectifier : �96%

Wide range of AC input voltage (85~300V
AC)

Super temperature performance for
rectifiers with the range
-
40


~ +75


Intelligent temperature control, ensures the
system to work stably

Intelligent battery management, prolong
battery lifetime

Easy installation: modules are hot
-
swappable, and enough user space

Remote monitoring, reduce operation
expenditure

Direct ventilation unit

Surge protection

SPD for

AC input



Class B surge protection



Standard surge discharge current: 30kA, 8/20s



Maximum surge discharge current: 60kA, 8/20s

SPD for

DC output



Differential mode: 10kA, 8/20s



Common mode: 20kA, 8/20s

SPD for

signal

input



Differential mode: 3kA, 8/20s



Common mode: 15kA, 8/20s

Fan speed line chart

Feature

80

85

90

95

100

0

5

10

15

20

25

30

35

40

45

50

55

%

A

50A rectifier efficiency curve

AC distribution

AC

input mode

Three phase five line mode (L1,L2,L3,N,PE) [single phase three line
mode (L, N, and PE)
and dual lines
input mode are available]

AC input voltage

85~300VAC, rated value

220VAC(L
-
N)

AC input frequency

45~65Hz,

rated value

50/60Hz

Power

factor



0.99

Main AC input

1 x 63 A /3P(MCB) ;

class
-
B surge protection ; D.G

connector

AC out
put port

1 x 10 A (MCB) with leakage protection for a maintenance socket
switch (optional)

DC distribution

Output voltage

43.2~58VDC, default
value
53.5VDC

Rated output
power



12000W, when 50A high

efficiency
modules configured



11600W, when 50A standard

efficiency
modules configured

Battery branch

2 x 125A (MCB)

LLVD

2 x 100A MCB, 6 x 20A MCB

BLVD

1x 32A MCB(TMC), 4 x 16A MCB(one for fan), 1 x 10A MCB(BBU)

Rectifier module

Input voltage

85~300VAC
,
rated value 220VAC

Input frequency

45~65Hz,

rated value 50/60Hz

Output voltage

42~58VDC,

rated value 53.5VDC

Efficiency



up

to
96% (48V/50A

high efficiency rectifier
)



up

to
92% (48V/50A

standard efficiency rectifier
)

Maximum output
power



30
00W (48V/50A

high efficiency rectifier
)



2900W (48V/50A

standard efficiency rectifier
)

Power monitoring unit

Rectifier module

Monitoring unit

Intelligent

battery
management



Battery floating/equalizing charge management



LLVD & BLVD



Battery discharging test



Battery remaining capacity testing



Battery temperature compensation



Battery disconnect / load shutdown

against over temperature


Real time

alarms


Real

time alarms through buzzer and indicator

System control



Rectifier module voltage/current regulation



Startup and shutdown of the rectifier module



Connect or disconnect batteries



Connect or disconnect load

Dormancy
management

According to the load power, the power system automatically starts the
dormancy mode of rectifier modules to save power

Remote monitoring



Supports

dry contacts alarms output



Communicates with
Huawei

main equipment through the
RS232/422/485. In addition, the SNMP(optional) communication
module enables the monitoring over the Ethernet.

TP48200A Outdoor

System

The
information in this document may contain predictive statements including, without limitation,
statements regarding the future financial and operating results, future product portfolio, new
to differ materially from those expressed or implied in the predictive statements. Therefore, such
information is

provided
for reference purpose only and constitutes neither an offer nor an
acceptance.
Huawei

may change the information at any time without notice.

Huawei

Industrial Base

Bantian
,
Longgang

Shenzhen 518129,
P.R.China

Tel: +86
-
755
-
28780808

www.huawei.com

DCDB

Power

meter